Universal Input Board
Universal Input board (UIBv2), 24VAC/20-60VDC-Sixteen (16) channel universal input board each capable of measuring 0-6/10VDC or 0/4-20mA, dry contact closures, thermistors, and current output temperature sensors. Built-in transducer support and Isolated M-Bus w/heartbeat. Up to three (3) can be networked to the ESB.
Summary
Specifications
Part Number – 130455
Capacities – 16 separate universal inputs 0-6 VDC, 0-10 VDC, 4-20 mA, or dry contact closures
Accuracy – 12 bit analog-to-digital converter, accurate to 1% of full range
Indicators and Controls
BUS XMIT – Indicates the board is sending data over the BUS
BUS RECV – Indicates the board is receiving data from the BUS
+5 – Indicates +5 volts DC is present
+10 – Indicates +10 volts DC is present
+24 – Indicates +24 volts DC is present
Switches – Three 8 position dip switches for bus address and board configuration
Termination – Two-piece pluggable terminal strips. Rated @ 250 VAC 15 amp. Terminals provided for M-BUS and power inputs.
Environmental – Operating Temp 32 to 120°F (0 to 49°C) 0-95% RH Non-condensing
Electrical – 48VDC max. load @ 0.125 amp, 24VDC max. load @ 0.250 amp, 24VAC max. load @ 0.370 amp
Size – 3.25 H x 10 W x 1.3 D in. (83 x 25 x 33 mm)
Weight – 1 lb (454 g)
Warranty – 1 Year
Optional Enclosures
Multiple Board Enclosure – Wall mounted with locking door; knockouts on all sides for electrical connections. Part Numbers 150774 and 150775 (requires external power supply)
Up to three boards per enclosure mounted in snaptrack
Dimensions – Enclosure 22 H x 15.25 W x 3.5 D in. (559 x 387 x 89 mm)
Weight – 20 lb (9 kg)
Single Board Expansion Enclosure – Part number 150860
Dimensions – 6 H x 15 W x 3.5 D in. (152 x 383 x 89 mm)
Weight – 4 lb (1.8 kg)
Specifications subject to change without notice.