Infrared Combustible Sensor Module

Proven Performance. Proven Technology. Proven Support.

Peripherals

TELSEC Controllers provide an integrated surveillance solution to monitor and control all environmental and access control functions and equipment alarming.

Acting as your smart eyes and ears, the TELSEC delivers large savings and quick payback.

icsm

A stand alone module with the intelligence to provide integral alarms. A base model already loaded with features you need: FM Approval for performance and safety, Aluminum or 316 Stainless Steel enclosure, 4-20 mA output, Modbus RTU RS-485 interface, Option for non-Methane gas configuration.

Summary

Information Technology (IT) at the component level! An infrared (IR) Combustible Gas sensor module with the brilliance to provide 4-20 mA and Modbus output. A stand alone module with the intelligence to provide integral alarms. A base model already loaded with features you need. A gas detector that is FactoryMutual approved and ready to manage your gas risk. The IR Gas Sensor Module provides all the built-in features desired by instrumentation and safety professionals.

Features

  • Local scrolling display.
  • Non-intrusive calibration,menu driven system.
  • FM Approved for performance and hazardous area operation, Class I, Div. 1, Group B, C, D. NEMA4X rated for -40° to 176°F areas.
  • Flexible Modbus, 4-20mA, Sentry bus, relay interface.
  • SIL Certified.

Specifications

Part Number – 150930
Sensor Type – Infrared, Dual Wavelength

Performance:
Default – 0-100% LEL Methane or Propane
User Setting – 0-100% by vol. Methane
Other Gases – %LEL Ethanol, Ethylene, Hexane, Butane, Propane, Pentane
Repeatability – ±1% LEL
Response Time – <10 sec to 60% full scale
Accuracy – ±1% for 0-50% LEL range, ±2% for 51-100% LEL range
Sensor Life – Typically >5 years

Output:
Display – Fixed and Scrolling LED
Relay – 0.25 Amp. High Alarm, Low Alarm, Trouble, all SPDT
Signal Output – Analog 4-20 mA (Trouble, 0 mA)
Optional Relays – Serial RS-485 Modbus RTU; 8 amp high, low

Electrical Data:
Power Consumption – 3 Watts
Connection Type – 3 or 4 wire
Input voltage – 24 VDC nominal: 10-30VDC

Operating Range:
Ambient Temp Range – -4° to 140°F (-20° to 60°C)
Relative Humidity – 5-99%

Construction:
Dimentions – (Al) 8.1 x 4.8 x 4.9 in. (21 x 12 x 12.cm), (SS) 7.5 x 4.4 x 4.9 in. (19 x 11 x 12 cm),
Weight – (Al) 2.7 lb. (1.3 Kg) — (SS) 5.4 lb. (2.6 Kg
Housing – Standard: Epoxy coated Aluminum, Optional: 316 Stainless Steel
Hazardous Area – Explosion proof, Class I, Div. 1
Classification – Groups B, C, D Class I, Zone 1; Group IIB+H2 IP66, IP65
Warranty – 90 days

Approvals:
FM Approval 6320 – Combustible Gas Detector Performance
FM Approval 3600SIL – Class I Div. 1, Groups B, C, D
Certified – FMEDA data for SIL-1
NFPA72 Compliant

Specifications subject to change without notice.